Digital EPIC D281, D291 ATEX
Download ETL21ATEX0055X-2200-Series-ATEX-EU-Type-Examination-Certificate-2.pdf
NEC/ATEX/IEC – Explosionproof with Aluminum or Stainless Steel enclosure
| Approvals | |
| Area classification (ATEX/IEC) | Ex II 2 GD |
| Ex db IIB+H2 T* Gb | |
| Ex tb IIIC T*°C Db IP6X | |
| Area classification (NEC/CEC) | Intertek ATM:103627517CRT-001 |
| Cl. I, Div. 1, Groups C & D; T* | |
| Cl. II, Div. 1, Groups E, F, and G; T* |
|
| Cl. I, Zone 1, AEx db / Ex db IIB+H2 T* Gb |
|
| Cl. I, Div. 2. Groups A, B, C & D; T* | |
| Zone 21, AEx tb / Ex tb IIIC T* Db IP6X | |
| Enclosure standards (ANSI/NEMA 250) | |
| All enclosures | Type 4, 4X, IP66/67 |
| Technical Data | |
| Transmitter Output | Polarity insensitive, two wire 4-20 mA, Namur NE43 |
| Transmitter Operating Voltage | 9 VDC - 30 VDC |
| Stroke | |
| Rotary: | 30° to 210° Potentiometer |
| 30° to 270° Non-contact sensor | |
| Switches | Magnum SPDT hermetically sealed switches with rhodium contacts |
| Magnum, SPDT hermetically sealed switches with tungsten contacts | |
| V3 mechanical switches, SPDT with gold-plated contacts | |
| Pepperl + Fuchs model NJ2-V3-N | |
| Enclosures | |
| D281 | Aluminum |
| D291 | Stainless Steel |