Digital EPIC D441/D450/D451 ATEX Ex ec
Download C-of-C-EPIC-441-450-451-530-540-550-Ex-ec-FM08ATEX0061XSupp07-1.pdf
NEC/ATEX/IEC – Non-Incendive or Intrinsically Safe with range of enclosure options
| Agency Approvals: | |
| Area classification | |
| D430 (NEC) | Class I, Div. 2, Groups A, B, C, D; T4 |
| Class II, Div. 2, Groups F, G; T4 | |
| Class III | |
| D441/D450/D451 (NEC/CEC) | Class I, Div. 1, Groups A, B, C, D; T4 |
| Class I, Div. 2, Groups A, B, C, D; T4 | |
| Class II, Div. 2, Groups F, G; T4 | |
| D441/D450/D451 (ATEX/IEC) | Ex II 3 G |
| Ex ec IIC T4 Gc | |
| D441/D450/D451 (ATEX/IEC) | Ex II 1 G |
| Ex ia IIC T4 Ga | |
| Tech Data: | *Ta = -40°C to +65°C for the factory fitted solenoid valve |
| *Ta = -40°C to +80°C when supplied without a solenoid valve | |
| Enclosure standards (ANSI/NEMA 250) | |
| D430 | IP55 |
| D441/D450/D451 | Type 4X and 6P, IP66, IP67 |
| IP67 for North America Only | |
| Enclosures | |
| D430 | Engineered resin |
| D441 | Aluminum |
| D450/D451 | Stainless steel |
| Falcon Solenoid Valves | |
| Cv: | Choice of 1.4, 3.5, 4.3 |
| Materials: | Brass, aluminium and stainless steel |
Digital EPIC D441/D450/D451 ATEX Ex ec
Download C-of-C-EPIC-441-450-451-530-540-550-Ex-ec-FM08ATEX0061XSupp07-1.pdf
Digital EPIC D441/D450/D451 ATEX Ex ia
Download C-of-C-EPIC-441-450-451-530-540-550-Ex-ia-FM08ATEX0062XSupp06-1.pdf
Digital EPIC D430 NEC
Digital EPIC D441/D450/D451 NEC
Digital EPIC D441/D450/D451 CEC